Flow with confidence

Booster sets, fire pumps and HVAC pumps, engineered for the building, not just delivered.

We size, supply, install, commission and service complete pumping systems for towers, hotels, hospitals, compounds and industrial plants across Egypt. It's the same work we've done since 1979, when our first site technician learned pumps on the Nile barges.

Pumping Solutions

Gabtic at a glance

Gabtic Engineering & Supplies is an Egyptian engineering company, founded in Cairo in 1979, that supplies, installs and services booster pump sets, fire pump packages and HVAC circulation pumps. It is an authorised partner of Armstrong Fluid Technology and Sulzer. It keeps pumps and spare parts in stock in Egypt, and runs a 24/7 service team for buildings where water or cooling can't stop.

Armstrong

Booster pump sets for buildings and compounds

A booster set keeps water pressure steady on every floor, from the ground-floor kitchen to the top-floor shower, at any time of day. We supply packaged Armstrong booster sets with:

  • Two or more pumps on a common base, in duty, assist and standby configurations
  • Variable-speed drives on each pump, so pressure stays constant while energy use follows demand
  • A pressure transducer, a pressure vessel, and a control panel that alternates the pumps and alarms on faults
  • Stainless-steel headers and isolation valves, pre-assembled and tested in Egypt

Used in: residential towers and compounds, hotels and resorts, hospitals, malls, office buildings, and industrial process water.

Booster sets: full product page
Booster pump sets for buildings and compounds

Armstrong UL/FM

Fire pump packages (UL/FM, NFPA 20)

Fire pumps have exactly one job: deliver design pressure the moment a sprinkler opens. We supply complete fire pump packages built to NFPA 20:

  • An electric main pump, a diesel standby pump and a jockey pump
  • UL-listed and FM-approved Armstrong fire pumps and controllers
  • Help with the paperwork and testing required for civil defence approval (الحماية المدنية)
Fire pumps: full product page
Fire pump packages (UL/FM, NFPA 20)

Armstrong Design Envelope

HVAC and chilled-water pumps

Circulation pumps for chilled-water and hot-water loops, from a single building up to district cooling:

  • Armstrong Design Envelope vertical in-line, horizontal end-suction and split-case pumps
  • Variable-speed, sensorless control, which saves energy on part-load days (most of the year)
  • Primary, secondary and condenser water duties

This is the same capability that delivered pumping for one of Africa's largest district cooling plants, at 60,000 tons of cooling.

HVAC pumps: full product page
HVAC and chilled-water pumps

Also supplied

Other pumps and pump-room equipment

  • SulzerSubmersible pumps and waste-water pumping stations
  • ArmstrongIPC and IPS pump controllers for energy optimisation
  • ArmstrongAir separators, expansion tanks and pressurisation units

Why Gabtic

Why buy pumps from Gabtic

References

Projects running on our pumps

ProjectPumping scope
Grand Egyptian MuseumArmstrong Design Envelope vertical in-line HVAC pumps
New Administrative CapitalArmstrong Design Envelope HVAC pumps, 630 kW
New Alamein CityArmstrong end-suction and split-case pumps; Sulzer domestic booster
Katameya DowntownArmstrong horizontal end-suction and split-case pumps
Four Seasons Sharm El SheikhArmstrong UL/FM fire pumps; Sulzer waste-water and submersible pumps
Bashtel Train StationArmstrong chilled-water pumps

Pump maintenance and service contracts

Annual contracts cover inspection, vibration and performance checks, seal and bearing replacement, and fire pump weekly and annual test support.

Schedule service

FAQ

Frequently asked questions

What is a booster pump set?

It's a package of two or more pumps with a controller and pressure vessel. It raises and holds water pressure in a building, switching pumps on and off and changing their speed to match demand.

How do I size a booster pump for a building?

Flow comes from the number and type of fixtures, adjusted for how many are likely to run at the same time. Head is the building's height, plus pipe losses, plus the pressure needed at the highest fixture. As a rough guide, allow about 3 m of head per floor, before losses. Send us the drawings and we'll size it properly.

What's the difference between a booster pump and a fire pump?

A booster pump serves everyday domestic water and runs continuously at variable speed. A fire pump is a dedicated, code-listed system that stays on standby and only runs in an emergency or during testing. The two must not be combined.

Do fire pumps in Egypt need UL/FM approval?

Most consultants and civil defence reviews in Egypt expect fire pumps and controllers to be UL-listed and/or FM-approved and installed to NFPA 20. Check the project specification. We supply compliant packages.

Do you service pumps you didn't supply?

Yes. Our service team maintains and repairs booster, fire and HVAC pumps whoever supplied them.

How fast can you deliver?

Stocked models ship from our warehouse in Egypt. Engineered packages depend on the specification. Ask us for the current lead time on your model.

Full pumping range

Pumps, controls and system accessories

9 products

Design Envelope 6800 Booster Set

Armstrong Fluid Technology

Design Envelope 6800 Booster Set

Packaged variable-speed Armstrong booster sets that hold constant water pressure on every floor of towers, compounds, hotels and hospitals. Irrigation duty is available subject to selection.

View product
Design Envelope 4300 Vertical In-Line Pump

Armstrong Fluid Technology

Design Envelope 4300 Vertical In-Line Pump

An intelligent vertical in-line pump with integrated variable-speed control for chilled-water and hot-water HVAC circulation, saving plant-room space and energy.

View product
Design Envelope 4200H End-Suction Pump

Armstrong Fluid Technology

Design Envelope 4200H End-Suction Pump

A horizontal end-suction pump with Design Envelope intelligent control for HVAC circulation where a base-mounted arrangement is preferred.

View product
4600 Horizontal Split-Case Pump

Armstrong Fluid Technology

4600 Horizontal Split-Case Pump

A horizontal split-case pump for larger HVAC circulation and water-transfer duties, with easy maintenance access to the rotating assembly.

View product
FireSet Horizontal Split-Case Fire Pump

Armstrong Fluid Technology

FireSet Horizontal Split-Case Fire Pump

A packaged horizontal split-case fire pump for fire-fighting water supply. UL/FM listing applies to the selected approved model, driver and controller package.

View product
Design Envelope IPS 4000

Armstrong Fluid Technology

Design Envelope IPS 4000

An integrated pump sequencing controller that stages multiple pumps for the lowest energy use while meeting system demand.

View product
Dirt and Air Separator

Armstrong Fluid Technology

Dirt and Air Separator

Removes entrained air and dirt from closed HVAC water circuits to protect pumps, coils and valves and keep systems running quietly and efficiently.

View product
Expansion Tanks

Armstrong Fluid Technology

Expansion Tanks

Hydronic expansion tanks that absorb thermal expansion and maintain stable system pressure, sized by volume, pressure and connection.

View product
ABS XFP Submersible Sewage Pumps

Sulzer

ABS XFP Submersible Sewage Pumps

Premium-efficiency submersible sewage pumps from Sulzer for wastewater and pumping-station duties, selected by motor, impeller and installation type.

View product